Page 101 - Building Regulation Design Guidelines - Architecture Book (Blue Code)
P. 101
SEcTION 12 HORIZONTAL CIRCULATION ELEMENTS SEcTION: 12 HORIZONTAL CIRCULATION ELEMENTS
12.1 ROUTE AccESS TO ThE SITE 12.3 cORRIDORS
12.1.1 Provision of points of ingress and egress shall be located to the 12.3.1 Corridors shall be clear from any obstruction, such as door
satisfaction of the Authority. opening or copy machine (figure -34). The minimum clear un-
obstructed width for public corridors shall be as follows:
12.1.2 All parts of the site to which vehicles may have access shall be
hard surfaced and drained to the satisfaction of the Authority.
Water Fountain Door Fully Open
12.1.3 All access locations and curb crossings shall require the approval
of the Authority. Public roadways carrying heavy volume of traffic Door
shall not be used for access unless there is no other practical A
Corridor Width Exit 0.18 m Exit
alternative. Max. 0.18 m Max.
12.1.4 The access routes for fire fighting shall be provided. Access
Door
B
12.1.5 The site and all improvements thereon shall be maintained in Door A and B Not Allowed
clean and tidy conditions.
Figure-34 Corridor Clear Width
12.2 ROUTE AccESS TO ThE BUILDING
12.2.1 Public and service entrances shall be clearly located and 12.3.1.1 Residential Types:
identified. a) 1.8 meter with rooms on both sides.
b) 1.5 meter with rooms on one side.
12.2.2 Location of the car parking to main entrance shall be clearly
identified.
12.3.1.2 Commercial Types:
12.2.3 Location of parking for people with disability from the main
entrance shall be identified. a) In general 3.0 meters
12.2.4 Identification of loading area location. b) In case of providing kiosks along the corridor of any
Commercial Building:
The maximum kiosk width shall be 1.8 meter.
(figure -35)
The minimum corridor width between the kiosks
and the adjacent shop or construction shall be 3.0
meters.
100 101