SECTION: 3  GUIDELINES FOR PRE STRESSED CONCRETE WORKS (SLABS)                       SECTION: 3   GUIDELINES FOR PRE STRESSED CONCRETE WORKS (SLABS)











                                  Dead end machine  Hydraulics Pump  Stressing Jack






                                  Grouting machine  Stapler gun  Duct Machine
                                                                                                                                       Fig. (3.5) Ducts
                                             Fig. (3.3) Pre stress equipment                                    e.   Duct Chairs, Fig. (3.6):
                                                                                                                    Chairs should be machine made and have epoxy coating for support
                          c.   Strands, Fig.(3.4):                                                                  parts and at least up to 20mm over the forms. Chairs distribution
                              Specialist contractor shall have strands supplier approval from                       shall be according to the specialist shop drawings, and should be of
                              Dubai Central Lab (DCL) and mill certificates.                                        6mm Diameter at least.











                                                                                                                                   Fig. (3.6) Ducts Chairs

                                           Fig. (3.4) Pre stress strands
                                                                                                                f.   Approval of shear stud :
                                                                                                                    Shear studs should be used in slabs with less than 200mm thickness
                          d.   Ducts:                                                                               if required by the design. Stud materials should be from specialized
                              Specialist  contractor  shall  apply  for  the  ducts  supplier  approval             qualified factory, Fig.(3.7).
                              along with all specifications and certificates. Specialist contractor
                              shall have ducts supplier approval along with all specifications and
                              certificates.
                              Thickness of duct should not be less than 0.4mm. The duct size
                              shall be suitable to accommodate the required strands, provided
                              that the net clear area for grouting should be more than twice the
                              ducts cross sectional areas.                                                                           Fig. (3.7) Shear stud
                              Corrugated and flat galvanized metal ducts are accepted, Fig. (3.5)