SEcTION  11  BUILDING STORIES /FLOOR TYPES                                 SEcTION:11  BUILDING STORIES /FLOOR TYPES







                11.1  BASEMENT                                                                      11.2  GROUND


                     A floor within building; can be totally under ground or partially with not          Any occupy-able floor not less than 0.15 meter than gate level.
                     less than half its height below gate level.
                                                                                                         11.2.1   A building/facility always has at least one ground floor, and may
                     11.1.1   The basement shall not extend beyond the plot limits.                             have more, as where a split-level entrance has been provided, or
                                                                                                                where a building is built into hillside.
                     11.1.2   The basement ceiling level shall not exceed 1.0 meter from the
                            gate level, for all building types. While it shall not exceed 1.3            11.2.2   The ground finishing floor level for all building types shall not
                            meter for residential villas.                                                       exceed  1.2  meter above  the  gate  level, except  the  residential
                                                                                                                villas which shall not exceed 1.5 meter.
                     11.1.3   The basement shall be connected to the super structure by
                            vertical circulations (staircases / elevators) with provision for            11.2.3   The ground floor shall be connected to the adjacent road by
                            fire-escape exits.                                                                  horizontal circulations such as lobby entrances and fire-escape
                                                                                                                exits which are deemed necessary for all types of buildings
                     11.1.4   The basement shall not be used for any individual facility and                    except for private villas.
                            should be used to serve the main building.
                                                                                                         11.2.4   For public buildings, common facilities such as prayer room and
                     11.1.5   The basement floor shall not be used for residential or,                          toilets for people with disability shall be provided at the ground
                            commercial use. It shall be restricted to the following functions:                  floor or at the nearest accessible floor.

                            a)  Car parks and service rooms for the building, such as: the               11.2.5  For mix used buildings, entrances leading to residential units
                              electrical room, telephone room and pump room.
                                                                                                                shall be separated from commercial spaces at the ground level.
                            b)  Tenants facilities (laundry room, drying room, swimming pool,
                              health club and its facilities, children’s playground and sports
                              facilities).
                     11.1.6   The minimum clear un-obstructed height of the basement and
                            semi basement for all types of functions shall be 2.4 meters from
                            FFL / Floor Finishing level till any suspended element or ceiling
                            soffits.

                     11.1.7   In the course of excavating, concreting, dewatering and casting
                            piling works for basement floor, care shall be taken to ensure all
                            safety precautions for the neighboring construction works.

                     11.1.8   Services requirements such as ventilation and drainage systems
                            etc. shall be as per E.H.S. regulations.