Page 52 - Building Regulation Design Guidelines - Architecture Book (Blue Code)
P. 52
SEcTION: 6 BUILDING/DEVELOPMENT CONTROL FACTORS SEcTION: 6 BUILDING/DEVELOPMENT CONTROL FACTORS
6.2.2 The gate/reference level of all building types shall not be less than 6.2.5 The internal clear (net) height of each floor for different building
0.30 meter above the approach road/s edge level and in case of types is the distance from the finished floor level to the finished
inclined longitude road, stepped ground level to be used to achieve ceiling level or any suspended element from ceiling as shown in
above relation between gate and road levels. table-1: (figure -10)
6.2.3 The ground finished floor level (GFFL) for all building types shall Maximum Net
Minimum Net
not exceed 1.2 meter above the adjacent road edge level except for Section No Building Types Height (meter) Height (meter)
residential villas which shall not exceed 1.5 meter. (figure-8)
6.2.5.1 Residential Type 2.7 4.2
6.2.4 In case of a plot located on two different road levels, the ground
6.2.5.2 Commercial Type
finished floor level (GFFL) for all building types shall not exceed 0.45
meter from high road edge level and 1.2 meter from the low road edge Ground floor 3.0 4.2
level. While (GFFL ) for villas shall not exceed 1.5 meter from the road
Ground floor with
edge level leading to the main entrance. (figure-9) Shops and Half Mezzanine 2.4 4.2
a)
Showrooms
Half Mezzanine 2.4 3.0
For All Building Types; Full Mezzanine 2.6 3.0
GFFL ≤ 0.45 m above Road 1
GFFL ≤ 1.2 m above Road 2 b) Office 2.5 3.0
c) Commercial Centers 4.2 6.0
For Villa; 6.2.5.3 Industrial Type
GFFL GFFL≤ 1.5 m from main
entrance road level
a) Warehouse and Factories 4.0 9.0
Road 1 6.2.5.4 Educational Type
High Level
Schools, Nurseries and Kindergar-
Road 2 a) 3.0 4.2
Low Level tens
6.2.5.5 Religious Type
According to the
a) Mosque 3.6 design and capacity
Figure-9 Ground Finished Floor Level (GFFL) of the mosque
for Plot Located on Different Road Level
6.2.5.6 Covered Parking Area 2.4 3.0
Table-1 Internal Clear Height for Different Building Types
50 51