Page 193 - Building Regulation Design Guidelines - Architecture Book (Blue Code)
P. 193
SEcTION: 17 SANITATION REQUIREMENTS SEcTION: 17 SANITATION REQUIREMENTS
17.3 PUBLIc SANITARY FAcILITIES Appliances Facility per Male Staff Facility per Female Staff
1 per 1-15 1 per 1-15
Every operational building must include provision of sanitary facilities,
2 per 16-30 2 per 16-30
unless otherwise permitted by the Authority.
WCs and 3 per 31-50 3 per 31-50
Washbasins
17.3.1 Sanitary facilities shall be provided at rates not less than the (no urinals 4 per 51-75 4 per 51-75
followings: provided) 5 per 76-100 5 per 76-100
a) Educational Building: For over 100 : plus 1 for For over 100 : plus 1 for
every Additional 25
Schools and Kindergartens: sanitary provisions at rates every Additional 25 or Part Thereof. or Part Thereof.
not less than mentioned in below table-17. 1 per 1-20
2 per 21-45
Appliances Kindergarten Special School School WCs and
Washbasins 3 per 46-75
1 per One Class with Size 1 per (urinals provided) 4 per 76-100
For Pupils 1 per 10 Pupils
WCs, Suitable to Children One Class
Washbasins For over 100 plus 1 for every Additional
and Urinals For Teachers 1 per 10 Classes with Minimum 2 for each Gender 25 Persons or Part Thereof, but 1 in 4 of
and Employees the additional Fittings may be a urinal.
Table-19 Sanitation Provisions for Offices and Shops
Table-17 Sanitation Provisions for Schools and kindergartens
Hotels: sanitary provisions at rates not less than mentioned
Nurseries: sanitary provisions at rates not less than in below table-20.
mentioned in below table-18.
Appliances Facility per Male Staff Facility per Female Staff
Appliances 1 per 100 up to 400. 2 per 100 up to 200,
WCs and For over 400, Add at the Rate of for over 200, Add at the Rate of
For Children 1 per 2 Kids Rooms Washbasins 1 per 250 Persons or Part Thereof.1 per 100 Persons or Part Thereof.
WCs and Washbasins
For Teachers and 1 per 10 Rooms with Minimum 2 for Urinals 1 per 50 Persons
Employees each Gender
Table-20 Sanitation Provisions for Hotels
Table-18 Sanitation Provisions for Nurseries
Restaurants and Cafes: sanitary provisions at rates not less
than mentioned in below table-21.
b) Religious Buildings:
Mosques: As mentioned in section -16, clause- 2. Appliances Facility per Male Staff Facility per Female Staff
1 per 100 up to 400. 2 per 100 up to 200.
WCs and
c) Commercial Building: Washbasins For over 400, Add at the For over 200, Add at the
Rate of 1 per 250 or Part Thereof. Rate of 1 per 100 or Part Thereof.
Offices and Shops: sanitary provisions at rates not less Urinals 1 per 25 persons
than mentioned in below table-19.
Table-21 Sanitation Provisions for Restaurants and Cafes
192 193