SEcTION: 13  VERTICAL CIRCULATION ELEMENTS  SEcTION: 13  VERTICAL CIRCULATION ELEMENTS



 13.3  FIRE-EScAPE STAIRcASES  13.3.3   A change in level of egress shall be achieved by an approved
                            means of egress where the elevation difference exceeds 0.54
 13.3.1   Fire-escape enclosure shall require construction, which is fireproof   meter.
 with sprinklers, alarms, fire detectors and fire resistant doors.
                            The maximum number of consecutive steps is 20, and minimum
 13.3.2   Fire-escape stairs design typess: (figure -48)  of 3 steps in the same direction. Maximum riser is 0.18 meter and
 1)  Spaced exterior stairs.  minimum tread is as per E.H.S. regulations.
 2)  Spaced interior stairs.  13.3.4   Staircases shall be totally enclosed in a fire resisting construction
 3)  Scissor stairs at core not allowed as per E.H.S..  materials and should lead directly to an exit at the ground floor
                            level. Doors leading to escape staircases shall be as per section
                            9.3.

                     13.3.5   Sufficient natural and mechanical lighting shall be provided with
                            minimum fresh air vents of 0.5 square meter in area, for each
                            floor.
 Spaced Exterior Stairs  13.3.6   The Fire-escape in all building types shall be clearly marked, and
                            provided with the minimum number of exits, according to E.H.S.
                            regulations.
                     13.3.7   Where an external stairway exists, it shall be ensured that in the
                            event of fire, it should not be blocked by smoke and flame from
 Spaced Interior Stairs     the openings (e.g. windows, doors).
                     13.3.8   The  design  of  staircases  shall  take  into  consideration  all  the
                            safety and fire fighting conditions and specifications approved
                            by the E.H.S..
                     13.3.9   The design of staircases shall be compartmentalized, fireproof
 Scissor Stairs at Core     and shall provide an exit stair or ramp arrangement for people
                            during emergency. The compartment shall have fire rated walls,
                            ceilings and doors with non-slippery flooring that can stand with
                            high heat temperature.

                     13.3.10  The staircase location shall be according to the following
                            requirements:
                            a) Easily approachable from any part of the building, in which
                              the farthest point shall not exceed 30.0 meters in distance.
 Door Swing Clearance         (figure -46)
 Usually Required  Scissor Stairs Separation
                            b) It shall be direct, leading to the external access approach
 Figure -48   Fire-escape Stairs Types  road.