Page 119 - Building Regulation Design Guidelines - Architecture Book (Blue Code)
P. 119

SEcTION: 13  VERTICAL CIRCULATION ELEMENTS                                         SEcTION: 13  VERTICAL CIRCULATION ELEMENTS



                13.3  FIRE-EScAPE STAIRcASES                                                             13.3.3   A change in level of egress shall be achieved by an approved
                                                                                                                means of egress where the elevation difference exceeds 0.54
                     13.3.1   Fire-escape enclosure shall require construction, which is fireproof              meter.
                            with sprinklers, alarms, fire detectors and fire resistant doors.
                                                                                                                The maximum number of consecutive steps is 20, and minimum
                     13.3.2   Fire-escape stairs design typess: (figure -48)                                    of 3 steps in the same direction. Maximum riser is 0.18 meter and
                            1)  Spaced exterior stairs.                                                         minimum tread is as per E.H.S. regulations.
                            2)  Spaced interior stairs.                                                  13.3.4   Staircases shall be totally enclosed in a fire resisting construction
                            3)  Scissor stairs at core not allowed as per E.H.S..                               materials and should lead directly to an exit at the ground floor
                                                                                                                level. Doors leading to escape staircases shall be as per section
                                                                                                                9.3.

                                                                                                         13.3.5   Sufficient natural and mechanical lighting shall be provided with
                                                                                                                minimum fresh air vents of 0.5 square meter in area, for each
                                                                                                                floor.
                      Spaced Exterior Stairs                                                             13.3.6   The Fire-escape in all building types shall be clearly marked, and
                                                                                                                provided with the minimum number of exits, according to E.H.S.
                                                                                                                regulations.
                                                                                                         13.3.7   Where an external stairway exists, it shall be ensured that in the
                                                                                                                event of fire, it should not be blocked by smoke and flame from
                      Spaced Interior Stairs                                                                    the openings (e.g. windows, doors).
                                                                                                         13.3.8   The  design  of  staircases  shall  take  into  consideration  all  the
                                                                                                                safety and fire fighting conditions and specifications approved
                                                                                                                by the E.H.S..
                                                                                                         13.3.9   The design of staircases shall be compartmentalized, fireproof
                      Scissor Stairs at Core                                                                    and shall provide an exit stair or ramp arrangement for people
                                                                                                                during emergency. The compartment shall have fire rated walls,
                                                                                                                ceilings and doors with non-slippery flooring that can stand with
                                                                                                                high heat temperature.

                                                                                                         13.3.10  The staircase location shall be according to the following
                                                                                                                requirements:
                                                                                                                a) Easily approachable from any part of the building, in which
                                                                                                                  the farthest point shall not exceed 30.0 meters in distance.
                                  Door Swing Clearance                                                            (figure -46)
                                  Usually Required       Scissor Stairs Separation
                                                                                                                b) It shall be direct, leading to the external access approach
                                 Figure -48   Fire-escape Stairs Types                                            road.