Page 118 - Building Regulation Design Guidelines - Architecture Book (Blue Code)
P. 118
SEcTION: 13 VERTICAL CIRCULATION ELEMENTS SEcTION: 13 VERTICAL CIRCULATION ELEMENTS
13.2 ELEcTRIc ELEVATORS 13.2.8 Elevators shall be provided with an electric closing system and a
warning device that signs on when the maximum load exceeds.
13.2.1 Elevators shall be provided in buildings that are higher than three It shall also have an emergency landing system, sufficient
floors depending upon the building or project requirements
mechanical ventilation, and suitable internal lighting.
13.2.2 For shopping malls higher than one floor, panoramic elevators, 13.2.9 Directional and warning labels shall be posted next to each door
with 10 person’s capacity are required.
inside the elevator showing total permissible weight, smoking
13.2.3 The following variables are involved in elevator selection: ban, proper use of elevator in case of fire, prohibiting small
children not accompanied by adults to use the system.
a) Travel distance.
b) Elevator speed. 13.2.10 All elevators shall be checked regularly to ensure proper working
order. The property owner must obtain a yearly certificate
c) Elevator capacity: The minimum capacity shall be 4 persons
per travel. confirming proper elevator’s functionality from the maintenance
company approved by the Authority.
d) Building population.
13.2.11 In shopping malls comprising of more than one floor, at least
e) Number and areas of the floors.
one elevator shall be designed for people with disability in
13.2.4 For buildings with a tower or corridor style, the installation of the accordance with International Standards. An electrically operated
elevators must be centralized. escalator is not a sufficient replacement to this elevator, except
if such escalator provided with an adaptable tread of at least 1.2
13.2.5 Elevators shall be clearly indicated and be located close to the meter long, and features necessary for people with disability.
staircase circulation. In case of mixed use buildings, elevators
leading to different uses shall be segregated. 13.2.12 An indoor lobby shall be provided for any elevator and shall be
equipped with mechanical lighting and ventilation.
13.2.6 At least one of the elevators shall be allocated for people with
disability. Refer to Authority’s related code.
13.2.7 Rooms built at the rooftop to house elevator equipment shall
satisfy the following:
a) Have dimensions that conform to the specifications and
measurements of the elevator’s manufacturing company.
b) Have a good air-conditioning system.
c) Have door openings that can be closed securely.
d) Operating wires and cables shall be concealed and be made
from anti rust material.
e) Have suitable cover for all moveable parts and components.