Page 59 - Dubai Universal Design Code
P. 59

5.11. Escalators, travellators and mechanical ramps

               Travellators are considered complementary elements of accessible pedestrian paths
               and shall have the following requirements:


               1.  The moving surface shall present a maximum gradient of ≤5%.


               2.  The beginning and the end of travellators shall present a contrasting pavement with
                   the surroundings.

               3.  The direction of travel shall be marked.


               4.  It is recommended to install an audio system indicating the start and end of these
                   devices.

               Escalators and mechanical ramps are not considered part of the accessible path.
               Whenever provided they shall be accompanied by a non-mechanical accessible
               alternative route or an elevator that leads to the different levels.


               5.12. Doors

               Doors connected to accessible paths must meet the following requirements:


               1.  Automatic doors are preferred for public building entrances and high pedestrian
                   traffic areas.


               2.  Doors should have a free passage width of minimum 900 mm. This free passage
                   must be measured between the face of the door and the face of the doorstop with
                   the door open at 90°.

               3.  Opening and closing mechanisms shall be placed between 900 mm and 1200 mm in
                   height and shall be easy to grasp and use. Pressure mechanisms or levers shall be
                   easy to operate with the elbow or be automatic.






















                                                                                                           58
   54   55   56   57   58   59   60   61   62   63   64