Page 76 - Building Regulation Design Guidelines - Architecture Book (Blue Code)
P. 76

SEcTION: 9  OPENINGS REQUIREMENTS  SEcTION: 9  OPENINGS REQUIREMENTS



 9.4  cOURTYARDS AND ShAFTS:  9.4.1.2  In residential apartments, natural lighting and ventilation
                                  for the maid’s room can be provided through the
 The minimum area of the courtyard and shaft for the natural lighting and   shafts, which shall be no less than 3.0 x 3.0 meters,
 ventilation requirements shall be as follows:
                                  regardless of the building height. If the building
 9.4.1  Habitable Spaces:         exceeds  ground  floor  plus  7  typical  floors,  Mechanical
 9.4.1.1   In case that the courtyard is common for many habitable   ventilation shall be provided in accordance to the
 spaces and floors, the minimum area for courtyard shall   specifications and conditions approved by the Authority.
 be square of 1/3 of the total floors height overlooking   (figure-22)
 at the courtyard and with minimum width of 6.0 X 6.0
 meters. (figure-21)              ≥ 3.0 m                    ≥ 2.1 m


 *L ≥ 6.0 m
 H-Floor Height
 Court
 Yard

                  ≥ 3.0 m          Court                *W    Maid's
                                    Yard
                                                               Room




                                                                *A


                      *A ≥ 6.50 m²  *W ≥ 10% A
                                Figure-22   Shaft for Maid's Room
 Court Yard
 *A  *L ≥ 6.0 m            9.4.1.3  Additional natural ventilation and lighting are required
 *L ≥ 6.0 m                       for rooms whose depth is more than three times its width.
                                  An opening or a shaft shall be in a minimum of 5% of the
                                  space area.
                     9.4.2  Service Spaces:
                           9.4.2.1  Closed Kitchens:  The minimum dimension of the shaft
 1
 *A=( X H) 2  and *L ≥6.0 m       shall be 3.0 x 3.0 meters regardless of the building height.
 3
                                  Mechanical ventilation shall be provided, if the building
 Figure-21   Court Yard for Habitable Spaces
                                  exceeds ground floor plus 7 typical floors in accordance
 *A = Floor Area / *L= Court yard Width  *A = Floor Area / *W= Window Area