Page 224 - Building Regulation Design Guidelines - Architecture Book (Blue Code)
P. 224

SEcTION  21  UTILITY SERVICES  SEcTION: 21  UTILITY SERVICES







 21.1  WATER SUPPLY TANKS  21.2.7   If  the  tanks  are  made  of  reinforced  concrete  and  non-porous
                            material, a minimum distance 1.0 meter shall be provided from
 21.1.1   Water supply tanks and installations shall comply with    the adjacent building and fence. If it is made of block work or
 the Authority‘s relevant code.   brick, a minimum distance of 3.0 meters shall be provided with a
 21.1.2   Water supply tanks shall be provided with lockable inspection   minimum depth of 1.5 meter from the level of the bottom surface
 openings of adequate size for cleaning process. Openings shall   of the pipe connected to the inlet.
 be located away from the direct day to day movements and
 sources of contamination, and shall be positioned higher than
 the floor level.   21.3  PLUMBING WORKS

 21.1.3   Design of tank shall take into consideration that the tank    21.3.1   Plumbing works shall comply with the Authority‘s relevant code.
 shall be free from sharp corners that may accumulate dirt or
 prevent thorough cleaning.  21.3.2   An inspection chamber shall be fitted at each point where the
                            direction of drainage pipes changes or at which the degree
 21.1.4   Location of water supply tanks shall be chosen as far as possible   of slope changes or at the junction of a branch and main line.
 from drainage network lines, inspection chambers, septic tanks   Distance between any two successive inspection holes shall not
 and soak ways.  In all cases, drainage pipe lines shall not be   exceed 15.0 meters.
 permitted to run above or next to water tanks in case such tanks
 are fitted underground.  21.3.3   No inspection chambers shall be constructed inside roofed
                            buildings except in shafts, service rooms, car sheds and
                            adequately ventilated corridors. Such chambers shall be of
 21.2  SEPTIc TANKS         dry type. Drainage pipes that extend underneath the flooring
                            and inside walls shall be protected from any external works or
 21.2.1   Septic tanks shall comply with the Authority‘s relevant code.
                            against settlement of floors.
 21.2.2   Septic tanks shall be within the plot limits.
                     21.3.4   All inspection chambers shall be dug within the plot limits.
 21.2.3   Septic tanks shall be located close to the approach road or
 alleyway and distanced from the main building and the adjacent   21.3.5   All basement levels shall be provided with appropriate means
 buildings to the plot. Location shall be subject to approval by the   and ways for drainage and filtration of water such as sand
 Authority and should be capable of being connected in future   separation rooms, pumps, grease traps, etc.
 with the public drainage network.
 21.2.4   Septic tank ceiling shall be made of reinforced concrete in order   21.4  RAINWATER DRAINAGE
 to withstand the load of vehicle traffic if necessary.
                     21.4.1   Rainwater drainage shall comply with Authority’s relevant code.
 21.2.5   Tanks shall have an opening of adequate size with a heavy duty
 lockable cover and top surface of the cover shall not rise above   21.4.2   The system for carrying rainwater from a roof shall be adequate.
 the finished ground level of the site in which it is situated.   The system shall carry the flow to an outlet to minimize the risk of
 21.2.6   Septic tanks shall  be  accessible  for  cleaning,  maintenance     blockage or leakage and be accessible for cleaning blockages.
 and  evacuating process.