 16.1.2  VILLAS ANNEXES: (figure -70)  Height ≤ 4.2 m
                                           Adjacent Neighbor   Plot
 a)  It is permitted to build annexes to residential villas with   Limit
 maximum height limited to ground floor only and without any   A1 = Annex 1
 set back from the plot boundary.  Area
                                       Corridor or Covered Passage
 b)  It can be used as private garages, servants quarter, external   ≥ 3.0 m  ≤ 3.0 m
 kitchen or as a sitting room (Majlis ), according to the following   wide
 conditions:
                       Adjacent                                     Adjacent
   The maximum height shall not exceed 4.2 meters from the   Neighbor  A = Villa Area  Neighbor
 adjacent neighbors and 4.5 meters from the approaching
 road or alleyway.
                                                         ≥ 3.0 m     Height ≤ 4.5 m
   The minimum set back shall be 3.0 meters between the
 annex and the main villa.
                                                          A2 = Annex 2
   The annex configuration shall be in a form of a row,    Area
 attached  to  the  plot  boundary,  or  with an  adequate   Plot  Road  Only allowable
                          Limit                                 opening is for a
 setback to allow for natural ventilation and lighting for the
                                             A1 + A2 ≤ 50% A    garage gate
 habitable spaces, or in order to install air conditioners.
                                        Figure-70    Villas Annexes
 c)  Annexes shall be used to serve the main building only. They
 shall not be used as independent units or for commercial
 purposes.

 d)  Its roof shall be limited for water tanks and air conditioner
 equipments.

 e)  It is forbidden to build a main staircase leading to its roof, if it
 is located next to the adjacent neighbors.

 f)  The annex may be connected to the main building by a covered
 passage or corridor with maximum width of 3.0 meters and
 same height as the annex.
 g)  The area of the annexes shall not exceed 50% of the main
 villa’s area.